Acopian R120N8T Single Output Redundant Power Supplies. Nominal Adjust Range ±V: 1 | Output Voltage: 120 | Case Size: 3R14 | Rack Mounting Model Simple Type: Power Supply

An Acopian Redundant Power Package is installed by simply connecting the AC input and DC output terminals. All wiring (including isolation diodes, output monitor circuits, switches, meters, adjustments and connectors) has been done for you.

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Applications- Redundant Power Packages should be considered for any equipment where the highest attainable reliability is essential, and an unexpected loss of power would be disastrous.
  • Input Redundancy- All Acopian Redundant Power Packages may be operated with only one AC power source. However, two isolated sets of AC input connections are provided, so that two independent sources o
  • Monitoring Circuitry- The Redundant Power Package contains two voltage monitoring circuits with relays, contacts of which are available to control external failure alarms or other circuitry.
  • Output Redundancy- Each Redundant Power Package contains two identical power supplies with their outputs interconnected through a diode switching arrangement that will detect any fault condition.
  • Overvoltage Protection- Automatic recovery. Each power supply contains an overvoltage protection circuit, to assure that neither power supply output will significantly exceed the nominal output voltag
  • Serviceability- A defective power supply can be rapidly and safely changed while the Redundant Power Package continues to furnish uninterrupted power to the load.
  • Theory of Operation- Each Redundant Power Package consists of the two power supplies installed in either a Rack Mounting or Wall Mounting assembly.

Specifications

    General
  • Alarm Relay Contact Ratings: 120 VAC, 8A / 60 Vdc, 1A. (To comply with SELV requirements, limit switched voltage to 60 Vdc / 42 VAC.)
  • Ambient Operating Temperature: -20 to +71°C.
  • Application: Computer; High Voltage; Instrumentation; Laser; Magnetic; Semiconductor / Thin Film; Telecommunications; Testing Equipment; Communication Systems, Process Controls
  • Backup mode: 0.2 volt less than nominal voltage shown in table.
  • Input Voltage: 105-125 VAC, 50-400 Hz, single phase.
  • Line Regulation: ±0.05%
  • Load Protection: Over voltage protection.
  • Load Regulation: ±0.05% (Dynamic regulation - does not include 0.2 volt shift which occurs during switching to lower-set backup supply.)
  • Number of Outputs: 1
  • Output Metering: A separate voltmeter for each output (standard). Ammeters available; see Options.
  • Overload/Short Circuit Protection: Fold back current limiting with automatic recovery.
  • Polarity: Output is floating; either positive or negative output terminal may be grounded or floated up to 300 volts above ground.
  • Product Category: Power Supplies
  • Remote Voltage Sensing: Provision for sensing the output voltage across the load, so that drops in the load line are compensated, is a standard feature.
  • Ripple: 1 mV rms.
  • Storage Temperature: -55 to +85°C.
  • Style: Enclosed Rack Mount
  • Temperature Coefficient: 0.02%/°C (Typical)
  • Voltage Monitor Circuits: One for each power supply. Relay contacts switch when output voltage decreases approximately 2 volts from the nominal rating (approximately 3 volts for outputs over 48 volts), and may be used to control an external failure alarm.

 